Health |
Resolved |
no changes to existing setup, no review required from health |
Inspections |
Resolved |
Provide a scalable plan showing all areas of the existing and combined space. Label each room as to the use of each room. |
Inspections |
Resolved |
Calculate the number of occupants in each room or space as per section 1004.1.2 and table 1004.1.2. Once you have recalculated the occupants show compliance with the fixture count per section 2902.1. |
Inspections |
Resolved |
What is the occupancy of this lease space. |
Inspections |
Resolved |
What will the total square footage be in the combined spaces? |
Inspections |
Resolved |
Is there currently a sprinkler in these lease spaces? |
Inspections |
Resolved |
If changes occur to the plans or specifications as a result of this review or for any other reason, revisions shall be issued as required and forwarded to this office. |
Inspections |
Resolved |
This building and its associated site shall be accessible per IBC Section 1009, Chapter 11 and ANSI. |
Inspections |
Resolved |
Complete and return the following form: ADAAG Conformance Statement (return copy, send original to address shown on the form) |
Inspections |
Resolved |
Fire extinguishers shall be provided per IBC Section 906 and during construction per IBC Section 3309. |
Inspections |
Resolved |
You will be required to provide egress illumination as described in IBC section 1008 and illuminated exit signs per section 1013. |
Inspections |
Resolved |
Where are the restrooms provide for the lease space? |