Description

Construct new 5-story, 67-unit apartment building with parking on the main level.

Details
Name Value
Sprinkler Required True
1st Floor Area (ft²) 21026.00
Number of Floors 3
2nd Floor Area (ft²) 17322.00
3rd Floor and Above Area (ft²) 51931.00
Basement Area Finished (ft²) 0.00
Total Basement Area (ft²) 0.00
Total Construction Area (ft²) 90279.00
Construction Height (ft) 60.00
Project Costs 10500000.00
Floodproof True
Flood Protection Elevation (FPE) 903.1'
Impervious Surface Area (ft²)
Below Grade Construction Slab on Grade
Foundation Type Poured Concrete
Number of Bathrooms
Number of Bedrooms
Total Land Disturbance Area (ft²)
Dwelling Units (DU) Added 67
Number of Exits
Building Use Group (Primary) R-2 Residential Multiple Family
Detailed Use Apartment
Establishment Name 1017 Apartments
Work Performed By Contractor
Roof Material
Electrical Work Yes - by Contractor
Plumbing Work Yes - by Contractor
Gas Piping Work Yes - by Contractor
Heating or Air Conditioning Work Yes - by Contractor
Crane Required
Contact Name Nathan Lotvedt
Business Associated With Kilbourne
Contact Phone Number 701-237-2279
Contact Email nathan@kcmfargo.com
Status Information
Name Complete Date
Application Submittal Yes 7/13/2021 9:21:26 AM
Completeness Review Yes 7/13/2021 9:21:31 AM
Plan Review Fee Payment Yes 7/13/2021 9:21:45 AM
Staff Review Yes 8/2/2021 10:37:06 AM
Returned for Revisions Yes 8/3/2021 7:41:18 AM
Resubmission Yes 11/14/2023 3:13:52 PM
Approval No
Issuance No
Certificate of Occupancy No
Finalize No
Fees
Type Amount Paid
Building $42,576.50 No
Plan Review $8,515.30 Yes
Reviews
Division Status Reviewer
Inspections Revisions Needed Peter Valkov
Engineering Revisions Needed Christine Goldader
Planning Revisions Needed Adam Martin
Fire Complete / Approved Ryan Erickson
WSEIA 41 Complete / Approved Peter Valkov
Review Comments
Division Status Comment
Planning Open Ground floor transparency is not met. Section 20-0212-3c of the City's Land Development Code requires a minimum of 35% of the ground floor facade to be transparent. The proposed elevations show a transparency of 562 SF, while a minimum transparency of 1371.21 SF is required.
Planning Open Provide a detail of the parking lot fence, showing the proposed height and materials.
Inspections Open Appears plans are showing a 5 stories above ground plane with a type V-A construction. IBC, table 504.4 shows only 4 stories are allowed for such a construction type. Please revise plans to show code compliance.
Planning Resolved Driveways must be spaced at a minimum of 50 feet. The plans show a proposed driveway spacing of 46 feet.
Inspections Open Sheet A002 doesn't clearly show all rated assemblies and their ratings. Please clarify plans to show all distinctive fire-rated/ smoke rated assemblies and resubmit.
Engineering Open Engineering Department comments for this project can be found under the parking lot project for the same address.
Inspections Open What is the rated listed assembly used for the 3-hour horizontal separation. Please provide.
Inspections Open Please provide all horizontal listed assemblies used in this project.
Inspections Open Plans show corridor on south-west side of the apartment levels that is not compliant with the maximum number of occupants per IBC, table 1006.2.1 as maximum number allowed is 20. Please revise plans to show code compliance.
Inspections Open Corridor on south-west side is also not compliant with IBC, table 1006.3.3(1) as such corridor is not allowed on levels fourth and above above level of exit discharge. Please revise plans to meet the code.
Inspections Open Is a two-way communication system provided per IBC, section 1009.8? Please confirm.
WSEIA 41 Resolved 903.1 required per WSEIA 41' area.
Inspections Open Please explain what fire rated assembly is used under the pedestal separation per IBC, section 510. Stairways show combustible materials below the pedestal and within the type I-A construction. Please note that any combustible materials used in the shafts under the 3 hour horizontal assembly shall be rated for 3 hours and provided with proper opening protectives. Please revise plans and resubmit.
Inspections Open How many Type "A" Units are designed for this facility? Please provide information, locations and detailing.
Inspections Open Is the elevator sized to accommodate an ambulance stretcher per IBC, section 3002.4? Please confirm.
Inspections Open It appears the west side exits/entrances are not accessible. Please explain how are these plans meeting the IBC, sections 1105 - accessible entrances and 1009.7 - areas of assisted rescue.
Inspections Open Club room #505 shows large glazed areas in a fire-rated wall assembly. It is not clear if the glazing is fire rated accordingly. Please provide information.
Inspections Open Club room #505 and rooftop patio #558 show sliding doors as part of the means of egress. Please note these are not allowed per IBC, section 1010.1.2 - door swing. Please revise plans to show proper doors.
Inspections Open Please provide number of occupants calculated for the Club Room #505 and Patio #558, as it is not clear how many people are to be accounted for these spaces.
Inspections Open Per IBC, section 1202.5 addresses natural ventilation for spaces intended for human occupation. Noted is that some interior bedrooms in thins buildings (e.g. units 308 & 310) do not have windows provided. Please explain how are such spaces provided with the required ventilation.
Inspections Open IBC, section 1204 requires spaces intended for human occupation to be provided with natural light. Please explain how are bedrooms per previous comment provided with the required natural light?
Inspections Open Some shafts appear to be not-rated in this building. Please provide rated enclosures for all shafts - elevator, stair, mechanical, etc. as required per IBC, section 713. Revise plans and resubmit.
Inspections Open Please provide information for rated shaft enclosures at the top - listed assemblies used, detailing and information.
Inspections
Type Date Status Inspection Items
Energy / Insulation Unscheduled
Footing Unscheduled
Foundation Unscheduled
UG Fire Unscheduled
Above Ceiling Building Unscheduled
Framing Unscheduled
Final Fire Unscheduled
  • Sprinkler system required - NFPA 13
  • Fire Alarm system required - low frequency sounders
  • Standpipes required
Final Building Unscheduled
Zoning Unscheduled
Final Parking Lot Unscheduled
Contractors
Name License
Kilbourne Construction Management LLC 54620A

Documents

View, download, and upload documents here.

Existing Documents
  • 21-0618_1017_ARCH-PERMIT.pdf (7/28/2021)
  • Planning Comments 2021-07-15.docx (7/15/2021)
  • Staff Comments 2021-08-02.doc (8/2/2021)
About This Site

This site allows you to search permit data on-line. You may also create an account to submit permit applications, track the progress, and make payments.

Need help?

We’ve created a webpage that explains each permit or registration step-by-step and gives you detailed information about fees, required forms and related items.

Online Help >
Report a Problem

Trouble with your application or inspection request? Give us a call! 701.241.1561