2006-0320-NEWC

Permit

New Building

Type

4302 17 Ave S

Location

Overview

A listing of the key features of the permit. To print this information, use the button below.

Printer Friendly Version

Description

Construct new building on previously permitted foundation.

Details
Name Value
Sprinkler Required True
1st Floor Area (ft²) 13787.00
Number of Floors 4
2nd Floor Area (ft²) 6866.00
3rd Floor and Above Area (ft²) 7432.00
Basement Area Finished (ft²) 1033.00
Total Basement Area (ft²) 1033.00
Total Construction Area (ft²) 30478.00
Construction Height (ft) 48.50
Project Costs 5600000.00
Impervious Surface Area (ft²)
Below Grade Construction Slab on Grade
Foundation Type Poured Concrete
Number of Bathrooms
Number of Bedrooms
Total Land Disturbance Area (ft²)
Dwelling Units (DU) Added
Number of Exits
Building Use Group (Primary) B Business
Detailed Use
Establishment Name RRHS Building
Work Performed By Contractor
Roof Material Single Ply Membrane
Crane Required
Contact Name Mark Singleton
Business Associated With Great States
Contact Phone Number 701-371-8791
Contact Email mark@greatstates.us
Status Information
Name Completed Date
Application Submittal Yes 6/9/2020 10:02:07 AM
Completeness Review Yes 6/9/2020 10:02:29 AM
Plan Review Fee Payment Yes 6/9/2020 10:02:39 AM
Staff Review Yes 6/26/2020 4:15:09 PM
Returned for Revisions Yes 7/1/2020 4:01:36 PM
Resubmission Yes 7/1/2020 4:01:41 PM
Staff Review Yes 7/1/2020 4:02:10 PM
Approval Yes 7/1/2020 4:02:18 PM
Issuance Yes 7/7/2020 1:50:37 PM
Certificate of Occupancy Yes 8/17/2021 2:07:30 PM
Finalize Yes 8/18/2021 12:19:38 AM
Fees
Type Amount Paid
Building $22,976.50 Yes
Plan Review $4,595.30 Yes
Reviews
Division Status Reviewer
Inspections Complete / Approved Peter Valkov
Planning Complete / Approved Kylie Bagley
Fire Complete / Approved Ryan Erickson
Inspections Complete / Approved Peter Valkov
Review Comments
Division Status Comment
Inspections Resolved Is the exterior canopy shown on drawings provided with sprinkler heads?
Inspections Resolved Please explain how is the common path from basement meeting the code requirements? It is not clear.
Inspections Resolved Is the stage shown on plans compliant with all applicable subsections to IBC, s. 410? It is not clear. Please comment and confirm.
Inspections Resolved Open sink required in kitchen 111
Inspections
Type Date Status Inspection Items
Investigation / Walk-Through 7/7/2021 Passed
Consultation 3/30/2021 Passed
Consultation 7/7/2021 Passed
Energy / Insulation 3/16/2021 Passed
Energy / Insulation 3/29/2021 Failed
Energy / Insulation 4/1/2021 Passed
Energy / Insulation 4/26/2021 Failed
Energy / Insulation 4/27/2021 Passed
Energy / Insulation 6/11/2021 Passed
Footing 8/26/2020 Passed
Foundation 5/11/2021 Passed
Slab 8/25/2020 Passed
Slab 1/12/2021 Passed
Slab 2/19/2021 Passed
UG Fire 9/18/2020 Passed
Framing 3/5/2021 Failed
Framing 3/10/2021 Passed
Framing 3/10/2021 Void
Framing 3/19/2021 Passed
Framing 4/21/2021 Passed
Framing 5/25/2021 Passed
Final Building 8/17/2021 Passed
Temporary Electrical Service 8/17/2020 Passed
Above Ceiling Electrical 6/16/2021 Passed
Above Ceiling Electrical 7/21/2021 Passed
Above Ceiling Electrical 7/29/2021 Passed
Rough Electrical 3/5/2021 Passed
Rough Electrical 4/20/2021 Passed
Rough Electrical 4/29/2021 Passed
Rough Electrical 5/11/2021 Passed
Rough Electrical 5/21/2021 Passed
Rough Electrical 7/9/2021 Passed
Electrical Service 4/20/2021 Passed
Final Electrical 8/13/2021 Failed
  • Door openers not GFCI'D.
  • Outside recepts. don't all work.
  • Need to properly ground outside recepts covers.
  • Label all breaker including "spares"
  • Need breaker lock for dishwasher.
  • Data rack recepts on 30A circuit but have 20A cord end.
  • TV recept. in 3rd flr men's bathroom and 2nd for both bathrooms not GFCI'D.
  • 3rd floor office and conference room have recepts. that don't work. SE and NE corner offices and S conference room.
  • Kitchen on 1st flr not all receptacles are GFCI'D
  • Need source label on disconnect for dishwasher on 1st floor. Also label what it is for.
  • 240v recept. in arts and crafts area needs GFCI protection. To close to sink.
  • Recept. by service is hooked up backwards.
  • Need tamper resistant receptacles in gymnasium.
  • Finish stage area.
  • Recepts. not working in gym.
  • Need listed panic hardware on electrical room door in gym.
  • Must label VFD'S as to which pump they are for.
  • Recepts. under stage area need to be GFCI'D.
  • Need to provide fault current labels for Rtu's 1-3
Final Electrical 8/17/2021 Failed
  • Door openers not GFCI'D.
  • Outside recepts. don't all work.
  • Need to properly ground outside recepts covers.
  • Label all breaker including "spares"
  • Need breaker lock for dishwasher.
  • Data rack recepts on 30A circuit but have 20A cord end.
  • TV recept. in 3rd flr men's bathroom and 2nd for both bathrooms not GFCI'D.
  • 3rd floor office and conference room have recepts. that don't work. SE and NE corner offices and S conference room.
  • Kitchen on 1st flr not all receptacles are GFCI'D
  • Need source label on disconnect for dishwasher on 1st floor. Also label what it is for.
  • 240v recept. in arts and crafts area needs GFCI protection. To close to sink.
  • Recept. by service is hooked up backwards.
  • Need tamper resistant receptacles in gymnasium.
  • Finish stage area.
  • Recepts. not working in gym.
  • Need listed panic hardware on electrical room door in gym.
  • Must label VFD'S as to which pump they are for.
  • Recepts. under stage area need to be GFCI'D.
  • Need to provide fault current labels for Rtu's 1-3
  • 2 RTU'S have available fault current that is higher than the SCCR of the RTU.
Final Electrical 11/3/2021 Passed
  • 2 RTU'S have available fault current that is higher than the SCCR of the RTU.
Plumbing Ground Work 8/24/2020 Failed
Plumbing Ground Work 8/25/2020 Passed
Above Ground Hydrostatic Test 7/20/2021 Failed
Above Ground Hydrostatic Test 7/29/2021 Passed
Final Fire Sprinkler 7/29/2021 Passed
Waste and Vent 2/26/2021 Failed
Waste and Vent 3/10/2021 Failed
Waste and Vent 3/31/2021 Failed
Waste and Vent 4/8/2021 Passed
Final Plumbing 8/10/2021 Passed
Final Fire Alarm 7/29/2021 Failed
Final Fire Alarm 7/30/2021 Passed
Above Ceiling Electrical 6/16/2021 Passed
Final Electrical 8/17/2021 Passed
Final Fire 7/29/2021 Passed
Contractors
Name License
Great States Construction 56184A

Documents

View, download, and upload documents here.

Existing Documents:
  • Construction Drawings.pdf (6/9/2020)
  • Permit Application.pdf (6/9/2020)
  • 19086 Stormwater Technical Memorandum - Signed and Compiled_20-8-18.pdf (8/19/2020)
  • 19086_C_20-8-18.pdf (8/19/2020)
  • 19086-Rendering_20-08-19.jpg (8/19/2020)
  • Certificate of Occupancy.doc (8/17/2021)
  • Permit.docx (7/7/2020)
  • CommentLetter1.doc (6/26/2020)
  • 20-007 City Review Response 6-30-20.pdf (7/1/2020)
  • 20-007 RRHS_ADAAG Conformance Statement_COPY.PDF (7/1/2020)
  • 20-073 Mechanical Plan Revision 2.pdf (7/1/2020)
  • 39910.pdf (7/1/2020)
About This Site

This site allows you to search permit data on-line. You may also create an account to submit permit applications, track the progress, and make payments.

Need help?

We’ve created a webpage that explains each permit or registration step-by-step and gives you detailed information about fees, required forms and related items.

Online Help >
Report a Problem

Trouble with your application or inspection request? Give us a call! 701.241.1561