2006-0320-NEWC

Permit

New Building

Type

4302 17 Ave S

Location

Overview

A listing of the key features of the permit. To print this information, use the button below.

Printer Friendly Version

Description

Construct new building on previously permitted foundation.

Details
Name Value
Sprinkler Required True
1st Floor Area (ft²) 13787.00
Number of Floors 4
2nd Floor Area (ft²) 6866.00
3rd Floor and Above Area (ft²) 7432.00
Basement Area Finished (ft²) 1033.00
Total Basement Area (ft²) 1033.00
Total Construction Area (ft²) 30478.00
Construction Height (ft) 48.50
Project Costs 5600000.00
Impervious Surface Area (ft²)
Below Grade Construction Slab on Grade
Foundation Type Poured Concrete
Number of Bathrooms
Number of Bedrooms
Total Land Disturbance Area (ft²)
Dwelling Units (DU) Added
Number of Exits
Building Use Group (Primary) B Business
Detailed Use
Establishment Name RRHS Building
Work Performed By Contractor
Roof Material Single Ply Membrane
Crane Required
Contact Name Mark Singleton
Business Associated With Great States
Contact Phone Number 701-371-8791
Contact Email mark@greatstates.us
Status Information
Name Complete Date
Application Submittal Yes 6/9/2020 10:02:07 AM
Completeness Review Yes 6/9/2020 10:02:29 AM
Plan Review Fee Payment Yes 6/9/2020 10:02:39 AM
Staff Review Yes 6/26/2020 4:15:09 PM
Returned for Revisions Yes 7/1/2020 4:01:36 PM
Resubmission Yes 7/1/2020 4:01:41 PM
Staff Review Yes 7/1/2020 4:02:10 PM
Approval Yes 7/1/2020 4:02:18 PM
Issuance Yes 7/7/2020 1:50:37 PM
Certificate of Occupancy Yes 8/17/2021 2:07:30 PM
Finalize Yes 8/18/2021 12:19:38 AM
Fees
Type Amount Paid
Building $22,976.50 Yes
Plan Review $4,595.30 Yes
Reviews
Division Status Reviewer
Inspections Complete / Approved Peter Valkov
Planning Complete / Approved Kylie Bagley
Fire Complete / Approved Ryan Erickson
Inspections Complete / Approved Peter Valkov
Review Comments
Division Status Comment
Inspections Resolved Is the exterior canopy shown on drawings provided with sprinkler heads?
Inspections Resolved Please explain how is the common path from basement meeting the code requirements? It is not clear.
Inspections Resolved Is the stage shown on plans compliant with all applicable subsections to IBC, s. 410? It is not clear. Please comment and confirm.
Inspections Resolved Open sink required in kitchen 111
Inspections
Type Date Status Inspection Items
Investigation / Walk-Through 7/7/2021 3:30:00 PM Passed
Consultation 3/30/2021 11:20:55 AM Passed
Consultation 7/7/2021 2:00:00 PM Passed
Energy / Insulation 3/16/2021 2:30:00 PM Passed
Energy / Insulation 3/29/2021 10:00:00 AM Failed
Energy / Insulation 4/1/2021 2:00:00 PM Passed
Energy / Insulation 4/26/2021 2:30:00 PM Failed
Energy / Insulation 4/27/2021 10:00:00 AM Passed
Energy / Insulation 6/11/2021 11:30:00 AM Passed
Footing 8/26/2020 3:43:06 PM Passed
Foundation 5/11/2021 9:45:00 AM Passed
Slab 8/25/2020 9:30:00 AM Passed
Slab 1/12/2021 1:00:00 PM Passed
Slab 2/19/2021 1:45:00 PM Passed
UG Fire 9/18/2020 1:30:00 PM Passed
Framing 3/5/2021 2:30:00 PM Failed
Framing 3/10/2021 1:30:00 PM Passed
Framing 3/10/2021 1:30:00 PM Void
Framing 3/19/2021 8:30:00 AM Passed
Framing 4/21/2021 10:15:00 AM Passed
Framing 5/25/2021 9:00:00 AM Passed
Final Building 8/17/2021 1:00:00 PM Passed
Temporary Electrical Service 8/17/2020 10:55:00 AM Passed
Above Ceiling Electrical 6/16/2021 1:00:00 PM Passed
Above Ceiling Electrical 7/21/2021 9:40:00 AM Passed
Above Ceiling Electrical 7/29/2021 10:10:00 AM Passed
Rough Electrical 3/5/2021 10:15:00 AM Passed
Rough Electrical 4/20/2021 11:30:00 AM Passed
Rough Electrical 4/29/2021 11:25:00 AM Passed
Rough Electrical 5/11/2021 11:00:00 AM Passed
Rough Electrical 5/21/2021 10:00:00 AM Passed
Rough Electrical 7/9/2021 11:30:00 AM Passed
Electrical Service 4/20/2021 11:15:00 AM Passed
Final Electrical 8/13/2021 10:30:00 AM Failed
  • Door openers not GFCI'D.
  • Outside recepts. don't all work.
  • Need to properly ground outside recepts covers.
  • Label all breaker including "spares"
  • Need breaker lock for dishwasher.
  • Data rack recepts on 30A circuit but have 20A cord end.
  • TV recept. in 3rd flr men's bathroom and 2nd for both bathrooms not GFCI'D.
  • 3rd floor office and conference room have recepts. that don't work. SE and NE corner offices and S conference room.
  • Kitchen on 1st flr not all receptacles are GFCI'D
  • Need source label on disconnect for dishwasher on 1st floor. Also label what it is for.
  • 240v recept. in arts and crafts area needs GFCI protection. To close to sink.
  • Recept. by service is hooked up backwards.
  • Need tamper resistant receptacles in gymnasium.
  • Finish stage area.
  • Recepts. not working in gym.
  • Need listed panic hardware on electrical room door in gym.
  • Must label VFD'S as to which pump they are for.
  • Recepts. under stage area need to be GFCI'D.
  • Need to provide fault current labels for Rtu's 1-3
Final Electrical 8/17/2021 10:30:00 AM Failed
  • Door openers not GFCI'D.
  • Outside recepts. don't all work.
  • Need to properly ground outside recepts covers.
  • Label all breaker including "spares"
  • Need breaker lock for dishwasher.
  • Data rack recepts on 30A circuit but have 20A cord end.
  • TV recept. in 3rd flr men's bathroom and 2nd for both bathrooms not GFCI'D.
  • 3rd floor office and conference room have recepts. that don't work. SE and NE corner offices and S conference room.
  • Kitchen on 1st flr not all receptacles are GFCI'D
  • Need source label on disconnect for dishwasher on 1st floor. Also label what it is for.
  • 240v recept. in arts and crafts area needs GFCI protection. To close to sink.
  • Recept. by service is hooked up backwards.
  • Need tamper resistant receptacles in gymnasium.
  • Finish stage area.
  • Recepts. not working in gym.
  • Need listed panic hardware on electrical room door in gym.
  • Must label VFD'S as to which pump they are for.
  • Recepts. under stage area need to be GFCI'D.
  • Need to provide fault current labels for Rtu's 1-3
  • 2 RTU'S have available fault current that is higher than the SCCR of the RTU.
Final Electrical 11/3/2021 12:30:00 PM Passed
  • 2 RTU'S have available fault current that is higher than the SCCR of the RTU.
Plumbing Ground Work 8/24/2020 2:30:00 PM Failed
Plumbing Ground Work 8/25/2020 1:15:00 PM Passed
Above Ground Hydrostatic Test 7/20/2021 10:00:00 AM Failed
Above Ground Hydrostatic Test 7/29/2021 2:00:00 PM Passed
Final Fire Sprinkler 7/29/2021 2:00:00 PM Passed
Waste and Vent 2/26/2021 2:45:00 PM Failed
Waste and Vent 3/10/2021 12:30:00 PM Failed
Waste and Vent 3/31/2021 10:45:00 AM Failed
Waste and Vent 4/8/2021 11:30:00 AM Passed
Final Plumbing 8/10/2021 3:30:00 PM Passed
Final Fire Alarm 7/29/2021 2:00:00 PM Failed
Final Fire Alarm 7/30/2021 11:00:00 AM Passed
Above Ceiling Electrical 6/16/2021 12:45:00 PM Passed
Final Electrical 8/17/2021 11:10:00 AM Passed
Final Fire 7/29/2021 2:00:00 PM Passed
Contractors
Name License
Great States Construction 56184A

Documents

View, download, and upload documents here.

Existing Documents
  • Construction Drawings.pdf (6/9/2020)
  • Permit Application.pdf (6/9/2020)
  • 19086 Stormwater Technical Memorandum - Signed and Compiled_20-8-18.pdf (8/19/2020)
  • 19086_C_20-8-18.pdf (8/19/2020)
  • 19086-Rendering_20-08-19.jpg (8/19/2020)
  • Certificate of Occupancy.doc (8/17/2021)
  • Permit.docx (7/7/2020)
  • CommentLetter1.doc (6/26/2020)
  • 20-007 City Review Response 6-30-20.pdf (7/1/2020)
  • 20-007 RRHS_ADAAG Conformance Statement_COPY.PDF (7/1/2020)
  • 20-073 Mechanical Plan Revision 2.pdf (7/1/2020)
  • 39910.pdf (7/1/2020)