2108-0085-NEWC

Permit

New Building

Type

1380 16 Ave N

Location

Overview

A listing of the key features of the permit. To print this information, use the button below.

Printer Friendly Version

Description

Construct new building for use as indoor sport practice facility. on 9/7/21 FND. issued for $ 3,339,084.00. Reminded the contractor that they will need to verify final value at the time the full permit is issued. PV

Details
Name Value
Sprinkler Required True
1st Floor Area (ft²) 100005.00
Number of Floors 1
2nd Floor Area (ft²)
3rd Floor and Above Area (ft²)
Basement Area Finished (ft²)
Total Basement Area (ft²)
Total Construction Area (ft²) 100005.00
Construction Height (ft) 78.00
Project Costs 23052087.00
Floodproof
Flood Protection Elevation (FPE)
Impervious Surface Area (ft²)
Below Grade Construction Slab on Grade
Foundation Type Poured Concrete
Number of Bathrooms
Number of Bedrooms
Total Land Disturbance Area (ft²)
Dwelling Units (DU) Added 0
Number of Exits
Building Use Group (Primary) A-3 Assembly General, Community Halls, Libraries, Museums
Detailed Use Amusement or Recreational
Establishment Name NDSU Indoor Practice Field
Work Performed By Contractor
Roof Material Metal
Electrical Work Yes - by Contractor
Plumbing Work Yes - by Contractor
Gas Piping Work Yes - by Contractor
Heating or Air Conditioning Work Yes - by Contractor
Crane Required
Contact Name David Stark
Business Associated With Kraus-Anderson
Contact Phone Number 612-804-0653
Contact Email david.stark@krausanderson.com
Contact Type
Contact Name Steve Skoblik
Business Associated With Foss
Contact Phone Number 701-499-7886
Contact Email steve@fossarch.com
Contact Type
Status Information
Name Complete Date
Application Submittal Yes 8/3/2021 1:15:02 PM
Completeness Review Yes 8/3/2021 1:18:14 PM
Plan Review Fee Payment Yes 8/10/2021 3:58:24 PM
Staff Review Yes 1/12/2022 8:50:42 AM
Approval Yes 1/12/2022 8:50:58 AM
Issuance Yes 1/12/2022 2:24:47 PM
Certificate of Occupancy Yes 10/3/2023 4:24:36 PM
Finalize Yes 10/3/2023 4:25:04 PM
Fees
Type Amount Paid
Building $92,788.50 Yes
Plan Review $21,228.90 Yes
Reviews
Division Status Reviewer
Inspections Complete / Approved Peter Valkov
Engineering Complete / Approved Christine Goldader
Planning Complete / Approved Kylie Bagley
Fire Complete / Approved Ryan Erickson
Floodplain Complete / Approved Peter Valkov
WSEIA 41 Complete / Approved Peter Valkov
Review Comments
Division Status Comment
Fire Resolved Is the field area intended for any other use? For example, an event with seating or standing on the field. (graduations, meals, etc) If so, please provide a code sheet with the maximum desired occupant load.
Engineering Resolved 1. What is happening with stormwater on this site? Recommend running a model for the proposed site and verifying that this will tie into the rest of the NDSU system.
Engineering Resolved 2. Add note stating “Excavation or other work in the right-of-way shall require a Traffic Control Plan that meets all Manual of Uniform Traffic Control Devices (MUTCD) requirements. This plan is required before any permits to work in the right-of-way will be issued.”
Engineering Resolved 3. Add note stating “Contractor shall coordinate with the City of Fargo Mains and Hydrants Department for all wet-tapping operations.”
Engineering Resolved 4. Add note stating “If a streetlight requires temporary or permanent relocation, contact Dave Helland at 701 241-1557.”
Engineering Resolved 5. Sheet C-1000 – Is the 12’ wide pavement south of the new field intended to be a driveway or sidewalk? According to the attachment, it is too close to University Dr N for a driveway.
Engineering Resolved 6. Sheet C-1030 – Indicate pipe material on water, storm, and sanitary sewer lines.
Engineering Resolved 7. Sheet C-1030 – We recommend that the direction of storm sewer flow only be changed within a structure. The storm sewer connection is approvable as submitted as it is on private property.
Engineering Resolved 8. Sheet C-1030 – Plumbing code requires a cleanout if sanitary sewer pipe fittings exceed 135 degrees. Add a cleanout to service on the west side of the building.
Engineering Resolved 9. Sheet C-1030 – Near the middle of the west side of the site, spacing between sanitary and storm pipes is less than 6”. Is there room to adjust either pipe? We would recommend adding insulation to prevent sanitary service from freezing.
Inspections Resolved Please submit a written request directed at the Building Official for approval of the additional height, as requested in sheet G100 of your plans set. Please explain why is the use of section 104.11 requested in a new building and provide supporting information to justify your request.
Inspections Withdrawn It appears the calculation of number of occupants for the indoor practice field is miscalculated. Please revise number to meet the requirement in the IBC, table 1004.5. Please verify space by space number of occupants and correct as required.
Inspections Resolved Please mark plans to show Alternate bid areas and explain if any alternates have been accepted by the owners.
Inspections Resolved Please explain the shortage of plumbing fixtures in a new facility. Plans show this design is short on plumbing fixtures, if alternates are accepted.
Inspections Resolved Original PEMB plans are required. Please submit a full construction set signed and stamped by respective structural engineer.
Inspections Resolved Plans are marked "Permit Set". City of Fargo only reviews final drawings intended for construction. Please submit your final plans for review.
Inspections Resolved Permit is issued for A-3 occupancy - indoor sport activities without spectator seating. No other events or public gatherings shall take place in this building.
Inspections Resolved Lower level roof requires roof access per IMC, section 306.5.
Floodplain Resolved NA
WSEIA 41 Resolved NA
Inspections
Type Date Status Inspection Items
Investigation / Walk-Through 3/29/2022 11:24:00 AM Passed
Investigation / Walk-Through 4/4/2022 9:00:00 AM Passed
Investigation / Walk-Through 9/21/2022 10:30:00 AM Passed
Investigation / Walk-Through 10/18/2022 2:28:35 PM Passed
Footing 3/29/2022 11:24:15 AM Passed
Footing 4/4/2022 8:00:00 AM Passed
Footing 7/20/2022 8:00:00 AM Failed
Footing 7/20/2022 11:30:00 AM Passed
Foundation 3/29/2022 11:00:00 AM Passed
Foundation 4/4/2022 11:00:00 AM Passed
Foundation 5/13/2022 1:00:00 PM Passed
Foundation 9/2/2022 11:00:00 AM Passed
Foundation 11/22/2022 8:15:00 AM Passed
Slab 7/6/2022 2:00:00 PM Passed
Slab 8/12/2022 3:00:00 PM Failed
Framing 6/23/2022 10:00:00 AM Passed
Framing 7/12/2022 8:15:00 AM Passed
Framing 8/2/2022 10:30:00 AM Passed
Framing 9/8/2022 10:30:00 AM Failed
Framing 6/12/2023 9:00:00 AM Failed
Framing 6/19/2023 9:00:00 AM Passed
Final Fire 7/28/2023 9:30:00 AM Passed
  • Sprinkler system required
  • Fire alarm system required - EVAC system required
Final Building 10/14/2022 10:45:00 AM Failed
Final Building 10/17/2022 2:00:00 PM Failed
Final Building 10/3/2023 2:01:39 PM Passed
Investigation / Walk-Through 4/12/2022 9:00:00 AM Passed
Footing 10/4/2021 2:30:00 PM Passed
Footing 10/5/2021 3:30:00 PM Passed
Footing 10/15/2021 9:00:00 AM Passed
Footing 10/18/2021 11:00:00 AM Passed
Footing 10/25/2021 9:00:00 AM Passed
Footing 11/4/2021 9:44:05 AM Passed
Footing 11/9/2021 9:00:00 AM Passed
Footing 11/16/2021 10:30:00 AM Passed
Footing 11/23/2021 8:45:00 AM Passed
Footing 11/30/2021 8:00:00 AM Passed
Footing 12/9/2021 2:24:59 PM Passed
Footing 12/9/2021 2:25:20 PM Passed
Footing 12/14/2021 8:30:00 AM Passed
Footing 12/15/2021 9:00:00 AM Passed
Footing 12/17/2021 9:30:00 AM Passed
Footing 12/22/2021 8:00:00 AM Passed
Footing 5/10/2022 9:00:00 AM Passed
Foundation 10/18/2021 11:00:00 AM Passed
Foundation 10/18/2021 3:30:00 PM Passed
Foundation 10/25/2021 8:00:00 AM Passed
Foundation 10/29/2021 11:30:00 AM Passed
Foundation 11/1/2021 8:00:00 AM Passed
Foundation 11/4/2021 10:00:00 AM Passed
Foundation 11/15/2021 8:30:00 AM Passed
Foundation 11/16/2021 9:00:00 AM Failed
Foundation 11/19/2021 8:45:00 AM Passed
Foundation 11/24/2021 1:00:00 PM Passed
Foundation 12/1/2021 11:00:00 AM Passed
Foundation 12/2/2021 11:00:00 AM Passed
Foundation 12/2/2021 3:30:00 PM Passed
Foundation 12/9/2021 9:45:00 AM Passed
Foundation 12/23/2021 12:00:00 PM Passed
Foundation 1/3/2022 1:00:00 PM Passed
Foundation 1/12/2022 9:45:00 AM Passed
Foundation 4/12/2022 9:00:00 AM Passed
Slab 5/19/2022 11:00:00 AM Passed
Final Foundation 9/15/2022 3:00:00 PM Passed
Investigation / Walk-Through 10/11/2022 10:15:00 AM Passed
Investigation / Walk-Through 10/11/2022 1:45:00 PM Passed
UG Electrical 3/10/2023 2:40:00 PM Passed
Above Ceiling Electrical 4/25/2023 11:20:00 AM Passed
Above Ceiling Electrical 5/24/2023 10:10:00 AM Failed
  • Pipes to close to roof decking.
  • MC cable not properly secured.
Above Ceiling Electrical 5/30/2023 9:30:00 AM Passed
  • Pipes to close to roof decking.
  • MC cable not properly secured.
Rough Electrical 7/27/2022 1:00:00 PM Passed
Rough Electrical 9/2/2022 10:40:00 AM Passed
Rough Electrical 9/20/2022 2:15:00 PM Passed
Rough Electrical 10/3/2022 10:00:00 AM Passed
Rough Electrical 1/4/2023 10:20:00 AM Passed
Rough Electrical 2/13/2023 9:45:00 AM Passed
Pool Bonding 3/3/2023 8:55:00 AM Failed
  • Bonding was done with stranded copper. Needs to be solid.
Pool Bonding 3/6/2023 8:30:00 AM Passed
  • Bonding was done with stranded copper. Needs to be solid.
Rough Electrical 3/30/2023 11:00:00 AM Passed
Rough Electrical 5/24/2023 10:00:00 AM Passed
Rough Electrical 6/8/2023 2:15:00 PM Passed
Rough Electrical 6/20/2023 10:10:00 AM Passed
Electrical Service 10/11/2022 10:40:00 AM Passed
Final Electrical 10/11/2022 10:10:00 AM Failed
  • Need fault current labels.
  • Need panel source labels.
  • Need to ground transformer
  • Need to bond building steel
  • Need bonding bushings on raceways that enter enclosures through concentric KO's.
  • Need to close up boxes.
  • Need canopies on corded luminaires.
  • Need more screws holding receptacle on raised covers
Final Electrical 10/13/2022 12:05:00 PM Failed
  • Need fault current labels.
  • Need panel source labels.
  • Need to ground transformer
  • Need to bond building steel
  • Need bonding bushings on raceways that enter enclosures through concentric KO's.
  • Need to close up boxes.
  • Need canopies on corded luminaires.
  • Need more screws holding receptacle on raised covers
  • Panel schedules
  • Need to provide a GFCI'D receptacle by all electrical panels, within the same room and within 25'
  • Make sure all transformers are grounded.
Final Electrical 10/17/2022 11:25:00 AM Failed
  • Need fault current labels.
  • Need panel source labels.
  • Panel schedules
  • Need to provide a GFCI'D receptacle by all electrical panels, within the same room and within 25'
  • Make sure all transformers are grounded.
Final Electrical 6/29/2023 11:00:00 AM Failed
  • Need fault current labels.
  • Need panel source labels.
  • Panel schedules
  • Need to provide a GFCI'D receptacle by all electrical panels, within the same room and within 25'
  • Make sure all transformers are grounded.
  • Bathroom receptacles need arc guards/spark rings.
  • Weight room receptacles in walls with rubber on the need arc guards/spark rings.
  • Need 1 GFCI'D receptacle in room with panel in the juice bar area.
  • Need all receptacles in juice bar area GFCI'D including menu board receptacles. GFCI needs to be readily accessible.
  • 200A disconnect on roof needs bonding bushing on raceway that enters through the bottom.
  • Double duplex in 2nd floor air handler room need more screws holding receptacles to the cover.
  • Need label at all panels indicating color of ungrounded & grounded conductors.
  • Need spark rings I data closet on 2nd floor, as receptacles are installed in walls with plywood on them.
  • Verify all water fountains are GFCI'D from readily accessible locations.
Final Electrical 6/30/2023 8:30:00 AM Failed
  • Need fault current labels.
  • Need panel source labels.
  • Panel schedules
  • Need to provide a GFCI'D receptacle by all electrical panels, within the same room and within 25'
  • Make sure all transformers are grounded.
  • Bathroom receptacles need arc guards/spark rings.
  • Weight room receptacles in walls with rubber on the need arc guards/spark rings.
  • Need 1 GFCI'D receptacle in room with panel in the juice bar area.
  • Need all receptacles in juice bar area GFCI'D including menu board receptacles. GFCI needs to be readily accessible.
  • 200A disconnect on roof needs bonding bushing on raceway that enters through the bottom.
  • Double duplex in 2nd floor air handler room need more screws holding receptacles to the cover.
  • Need label at all panels indicating color of ungrounded & grounded conductors.
  • Need spark rings I data closet on 2nd floor, as receptacles are installed in walls with plywood on them.
  • Verify all water fountains are GFCI'D from readily accessible locations.
Final Electrical 8/4/2023 12:50:00 PM Failed
  • Make sure all transformers are grounded.
  • Bathroom receptacles need arc guards/spark rings.
  • Need all receptacles in juice bar area GFCI'D including menu board receptacles. GFCI needs to be readily accessible.
  • Tub area---Receptacle o. East wall by sink needs to be GFCID and needs arc guard.
  • Room 116B & 116B1-- make sure receptacles are GFCI'D
  • Training room.Need arc guards in gender neutral bathroom
  • Need to make sure GFCI modules are listed.
Final Electrical 8/17/2023 10:00:00 AM Failed
  • Make sure all transformers are grounded.
  • Bathroom receptacles need arc guards/spark rings.
  • Need all receptacles in juice bar area GFCI'D including menu board receptacles. GFCI needs to be readily accessible.
  • Tub area---Receptacle o. East wall by sink needs to be GFCID and needs arc guard.
  • Room 116B & 116B1-- make sure receptacles are GFCI'D
  • Training room.Need arc guards in gender neutral bathroom and in tub room by sink.
  • Need to make sure GFCI modules are listed.
  • Need label on service that therexis an on site Standby power source and where it is located.
  • Need to mark Sccr on front of ATS'S.
  • Chiller needs to be hooked up.
Final Electrical 9/22/2023 2:30:00 PM Passed
  • Training room.Need arc guards in gender neutral bathroom and in tub room by sink.
  • Need to make sure GFCI modules are listed.
  • Need label on service that therexis an on site Standby power source and where it is located.
  • Need to mark Sccr on front of ATS'S.
  • Chiller needs to be hooked up.
UG Fire 8/4/2022 12:00:00 PM Passed
Above Ground Hydrostatic Test 8/22/2022 10:00:00 AM Failed
Above Ground Hydrostatic Test 10/10/2022 11:00:00 AM Passed
Rough Fire Sprinkler 10/13/2022 3:15:00 PM Passed
Fire Pump Test 10/10/2022 1:00:00 PM Passed
Fire Pump Test 4/26/2023 1:00:00 PM Passed
Final Fire Sprinkler 4/26/2023 1:00:00 PM Passed
Final Electrical 8/17/2023 10:15:00 AM Passed
Contractors
Name License
Kraus-Anderson Construction Co 3237A

Documents

View, download, and upload documents here.

Existing Documents
  • City of Fargo _ Permitting & Licensing.pdf (12/6/2021)
  • NDSU-IPF_Civil-ChangeDirective#2_8-30-21.pdf (12/6/2021)
  • B3020769 Phase Final_Rev_R3_Review Complete SS (11.30.2021) PHASE 1.pdf (1/12/2022)
  • B3020769 Special Plate_Angle (11.18.2021) PHASE 1.pdf (1/12/2022)
  • C3020769 Phase Final_Review Complete SS (12.09.2021) PHASE 2.pdf (1/12/2022)
  • C3020769 Special Angle_Plate (12.09.2021) PHASE 2.pdf (1/12/2022)
  • D3020769 Phase Final_Review Complete SS (12.09.2021) PHASE 3.pdf (1/12/2022)
  • D3020769 Special Angle_Plate (12.09.2021) PHASE 3.pdf (1/12/2022)
  • E3020769 Phase Final_Review Complete SS (12.09.2021) PHASE 4.pdf (1/12/2022)
  • E3020769 Special Angle_Plate (12.09.2021) PHASE 4.pdf (1/12/2022)
  • F3020769 Phase Final_Review Complete SS (12.09.2021) PHASE 5.pdf (1/12/2022)
  • F3020769 Special Plate_Angle (12.09.2021) PHASE 5.pdf (1/12/2022)
  • Final Stamped PEMB Drawings а (1).pdf (1/12/2022)
  • G3020769 Phase Final_Review Complete SS Rev_R00 (2022.01.06) PHASE 6.pdf (1/12/2022)
  • G3020769 Special Plate-Angles Rev_R00 (20220106).pdf (1/12/2022)
  • NDSU-IPF - PERMIT - Drawings.pdf (8/19/2021)
  • NDSU-IPF - PERMIT - Specifications.pdf (8/19/2021)
  • Certificate of Occupancy.pdf (10/3/2023)
  • Final Stamped PEMB Drawings.pdf (10/1/2021)
  • Permit.docx (1/12/2022)
  • Planning Approval Packet - 1380 16 Ave N (NDSU Indoor Practice Field).pdf (7/7/2022)
  • Receipt.pdf (8/10/2021)
  • Staff Comments 2021-08-24.doc (8/24/2021)
  • 1901 NDSI IPF Plan Review Response.pdf (8/30/2021)
  • ADAAG-ND-CONFORMACE.pdf (8/30/2021)
  • Fargo-NDSU-IPF special-inspec-summary.pdf (8/30/2021)
  • FW NDSU Practice Field.msg (5/5/2022)
  • FW NIFPC - Steam Vault - Structural Drawings.msg (5/5/2022)
  • FW Special inspections form for NDSU Steam Vault FW Attached Image.msg (5/5/2022)
  • NDSU IPF COMcheck - Envelope Compliance Report.pdf (8/30/2021)
  • NDSU IPF COMcheck Mech.pdf (8/30/2021)
  • NDSU IPF Lighting Compliance Forms.pdf (8/30/2021)
  • NDSU-IPF - FINAL - Drawings.pdf (8/30/2021)
  • NDSU-IPF Alt Design Request Letter.pdf (8/30/2021)
  • NDSU-IPF_G100 R1.com.pdf (9/7/2021)
  • RE 1380 16 Ave N.msg (8/5/2021)
  • Special inspections form for NDSU Steam Vault FW Attached Image.msg (5/5/2022)