2105-0951-NEWC

Permit

New Building

Type

4475 Calico Dr S

Location

Overview

A listing of the key features of the permit. To print this information, use the button below.

Printer Friendly Version

Description

Silverstar Car Wash - Tunnel Car Wash with Office, Lobby, Restrooms, & Mechanical Room. Site Features vacuums, trash enclosure and an accessory building for mat cleaners and vending. Required to be Floodproofed by WSEIA to an elevation of 907.80.

Details
Name Value
Porch False
Solar Energy System False
Fireplace False
Garage False
Deck False
Work Performed By Contractor
Occupant Load 21
Below Grade Construction Slab on Grade
Foundation Type Poured Concrete
Number of Bathrooms 1.00
Number of Bedrooms 0
Total Land Disturbance Area (ft²)
Dwelling Units (DU) Added 0
Number of Exits 2
Building Use Group (Primary) B Business
Detailed Use Other
Establishment Name Silverstar Car Wash
Sprinkler Required False
1st Floor Area (ft²) 4134.00
Number of Floors 1
2nd Floor Area (ft²) 0.00
3rd Floor and Above Area (ft²) 0.00
Basement Area Finished (ft²) 0.00
Total Basement Area (ft²) 0.00
Total Construction Area (ft²) 4134.00
Construction Height (ft) 24.00
Project Costs 1138387.00
Floodproof False
Flood Protection Elevation (FPE)
Contact Name Wade Behm
Contact Type General Contractor
Business Associated With Hegg Construction
Contact Phone Number 6053666252
Contact Email wbehm@heggconstruction.com
Number of Small Plant Units 114
Number of Larg Plant Units 3
Electrical Work Yes - by Contractor
Plumbing Work Yes - by Contractor
Gas Piping Work Yes - by Contractor
Heating or Air Conditioning Work Yes - by Contractor
Crane Required True
Impervious Surface Area (ft²) 30132.00
Roof Material Single Ply Membrane
Contact Name Mike Seeloff
Contact Type General Contractor
Business Associated With Hegg Construction
Contact Phone Number 509.570.8932
Contact Email mseeloff@heggconstruction.com
Contact Name Travis Stuntebeck
Contact Type Architect
Business Associated With VanDeWalle Architects
Contact Phone Number 6053394411
Contact Email travis@vandewallearchitects.com
Contact Name Brian Pattengale
Contact Type Civil Engineer
Business Associated With Houston Engineering
Contact Phone Number 701.237.5065
Contact Email bpattengale@houstoneng.com
Status Information
Name Complete Date
Application Submittal Yes 5/28/2021 8:50:27 AM
Completeness Review Yes 6/3/2021 1:05:02 PM
Plan Review Fee Payment Yes 6/4/2021 8:47:30 AM
Staff Review Yes 6/9/2021 11:11:59 AM
Approval Yes 6/22/2021 10:09:20 AM
Issuance Yes 6/22/2021 12:24:54 PM
Certificate of Occupancy Yes 4/6/2022 7:52:52 AM
Finalize Yes 4/7/2022 12:04:03 AM
Fees
Type Amount Paid
Building $5,132.50 Yes
Plan Review $1,026.50 Yes
Reviews
Division Status Reviewer
Inspections Complete / Approved Doug Desotel
Engineering Complete / Approved Roger Kluck
Planning Complete / Approved Kylie Bagley
Fire Complete / Approved Ryan Erickson
Federal Aviation Administration Complete / Approved Doug Desotel
Floodplain Complete / Approved Doug Desotel
WSEIA 41 Complete / Approved Doug Desotel
Review Comments
Division Status Comment
Engineering Resolved Engineering Department comments for this project can be found under the parking lot project for the same address.
Planning Resolved Planning Department comments for this project can be found under the parking lot project for the same address.
Inspections Resolved Sheet 2, The accessible parking space does not comply with section 1106.6. Shall be located on the shortest accessible route to the building entrance.
Inspections Resolved Calculate the number of occupants in each room or space as per section 1004.1.2 and table 1004.1.2. Once you have recalculated the occupants show compliance with the fixture count per section 2902.1.
Inspections Resolved Sheet A0.1 Code plan, The building Envelope Requirements are not correct for climate Zone #7.
Inspections Open Special inspections and reporting (if required) shall be provided on this project per IBC Sections 1704 and 1705. The permit applicant shall submit a statement of special inspections as required by IBC Sections 1704 and 1705. A copy of a summary is attached for your use. Please provide a list of special inspectors and their qualifications. Special inspector shall provide this office with a final report documenting required special inspections and correction of any discrepancies noted in the inspections as required by IBC Section 1704.2.4. A certificate of occupancy may not be issued for this project until the final report is received by this office. (6/16 Deferred submittal)
Inspections Open Provide information on compliance with the International Energy Conservation Code 2018. Comply with IECC Sections 401-405 or 407 as required. Computer-generated documentation (e.g. ComCheck) will be allowed to indicate total building performance as per IECC Section 407.6. Your summary must include building envelope, mechanical systems, water heating, interior lighting and electrical power systems.(6/16 Envelope complies with the table)
Inspections Resolved This building and its associated site shall be accessible per IBC Section 1009, Chapter 11 and ANSI.
Inspections Resolved Complete and return the following form: ADAAG Conformance Statement (return copy, send original to address shown on the form)
Inspections Resolved Please provide the Geotechnical report for the building site. (6/16 I did not receive)
Inspections Resolved Per IBC section 1109.5 and Chapter 29 you are required to provide drinking fountains. Please provide locations and types on your plans.
Inspections Resolved Per IBC Chapter 29 you are required to provide a service sink. Please provide location on plans and the wall surfaces. ( 6/10 Plan note #268 on A2.0 references a utility sink)
Inspections
Type Date Status Inspection Items
Investigation / Walk-Through 4/4/2022 2:00:00 PM Passed
Investigation / Walk-Through 12/27/2022 1:00:00 PM Passed
Footing 6/30/2021 1:00:00 PM Passed
Footing 9/23/2021 12:00:00 PM Passed
Foundation 9/27/2021 9:00:00 AM Passed
Above Ceiling Building 2/2/2022 2:15:00 PM Passed
Framing 12/1/2021 9:00:00 AM Passed
Certificate of Occupancy 4/5/2022 11:30:00 AM Passed
Final Building 4/4/2022 2:00:00 PM Failed
Final Building 4/5/2022 11:45:00 AM Passed
Investigation / Walk-Through 2/18/2022 9:55:00 AM Passed
Temporary Electrical Service 7/23/2021 10:00:00 AM Failed
  • Need to either get rid of the 50A receptacle or GFCI and install a 50A breaker.
Temporary Electrical Service 7/27/2021 9:05:00 AM Passed
  • Need to either get rid of the 50A receptacle or GFCI and install a 50A breaker.
Above Ceiling Electrical 1/31/2022 1:50:00 PM Passed
Rough Electrical 10/29/2021 11:47:00 AM Passed
Rough Electrical 3/17/2022 1:30:00 PM Passed
Electrical Service 1/13/2022 10:35:00 AM Passed
Final Electrical 3/28/2022 1:00:00 PM Failed
  • Need GFCI'D receptacle in electrical room.
  • Need to GFCI receptacles in laundry area including dryer
  • GFCI receptacle in break area by glass door.
  • Fans forced heater needs breaker lock off.
  • Check mat cleaning area, as it wasn't done.
Final Electrical 4/4/2022 8:40:00 AM Passed
  • Need GFCI'D receptacle in electrical room.
  • Need to GFCI receptacles in laundry area including dryer
  • GFCI receptacle in break area by glass door.
  • Fans forced heater needs breaker lock off.
  • Check mat cleaning area, as it wasn't done.
Final Electrical 5/2/2022 10:30:00 AM Passed
  • Need to GFCI receptacles in laundry area including dryer
Plumbing Ground Work 8/5/2021 4:15:00 PM Passed
Waste and Vent 11/4/2021 10:00:00 AM Failed
Waste and Vent 3/15/2022 2:00:00 PM Passed
Final Plumbing 3/15/2022 2:30:00 PM Passed
Sewer Service 9/1/2021 11:15:00 AM Failed
Sewer Service 9/3/2021 12:30:00 PM Failed
Sewer Service 9/7/2021 1:45:00 PM Passed
Sewer Service 10/6/2021 10:15:00 AM Passed
Contractors
Name License
Hegg Construction 44352A

Documents

View, download, and upload documents here.

Existing Documents
  • Silverstar 45th Street ND-1 Specifications.pdf (6/3/2021)
  • Silverstar ND-1 Combined Set 5.28.21.pdf (6/3/2021)
  • Certificate of Occupancy.doc (4/6/2022)
  • Permit.docx (6/22/2021)
  • Receipt.doc (6/22/2021)
  • Receipt.doc (6/3/2021)
  • RE Permit 2105-0951-NEWC (NEWC-COMM).msg (6/3/2021)
  • Architects response 1 4475 Calico Dr S Permit #2105-0951-NEWC and 2106-0145-PRKG.msg (6/16/2021)
  • Geotechnical report 4475 Calico Dr S Permit #2105-0951-NEWC and 2106-0145-PRKG.msg (6/16/2021)
  • Message from designer Silverstar Car Wash (4475 Calico Drive S).msg (6/10/2021)
  • Plan Review 1.doc (6/9/2021)
  • Plan Review 2 4475 Calico Dr S Permit #2105-0951-NEWC and 2106-0145-PRKG.msg (6/16/2021)
  • Revised plans 2 4475 Calico Dr S Permit #2105-0951-NEWC and 2106-0145-PRKG.msg (6/16/2021)
About This Site

This site allows you to search permit data on-line. You may also create an account to submit permit applications, track the progress, and make payments.

Need help?

We’ve created a webpage that explains each permit or registration step-by-step and gives you detailed information about fees, required forms and related items.

Online Help >
Report a Problem

Trouble with your application or inspection request? Give us a call! 701.241.1561