Fire |
Withdrawn |
Without fire protection systems in accordance with International Fire Code section 3206.2, high-piled combustible storage (12'+) will be limited 500 square feet (or less) for the entire building. |
Engineering |
Resolved |
Provide written permission from the neighborhood association to connect to the private sanitary sewer holding tank. |
Inspections |
Resolved |
Will you be constructing the mezzanine in unit 1?(9/21 Yes) |
Inspections |
Resolved |
The mezzanine in unit 1 exceeds the area limitation as per section 502.1.(9/21 new plan submitted) |
Inspections |
Resolved |
What will the mezzanine be used for, will this be an occupied space? Section 1011.16 (Ladder)(9/21 Storage) |
Inspections |
Resolved |
If changes occur to the plans or specifications as a result of this review or for any other reason, revisions shall be issued as required and forwarded to this office. |
Inspections |
Resolved |
A copy of this review, all responses, plans or specifications changes, or any other subsequent information pertaining to this project shall be provided to the contractor for his information. |
Inspections |
Resolved |
This building and its associated site shall be accessible per IBC Section 1009, Chapter 11 and ANSI. |
Inspections |
Resolved |
Complete and return the following form: ADAAG Conformance Statement (return copy, send original to address shown on the form) |
Inspections |
Resolved |
Fire extinguishers shall be provided per IBC Section 906 and during construction per IBC Section 3309. |
Inspections |
Resolved |
You will be required to provide egress illumination as described in IBC section 1008 and illuminated exit signs per section 1013. |
Inspections |
Resolved |
There shall be no hazardous materials in this building over the allowable quantities per IBC Sections 307 and 414. Please verify and respond. |
Inspections |
Resolved |
There is a maximum of ½” height for the thresholds into the building per IBC Section 1010.1.7. |
Inspections |
Resolved |
Sheet S002,Special inspections and reporting (if required) shall be provided on this project per IBC Sections 1704 and 1705. The permit applicant shall submit a statement of special inspections as required by IBC Sections 1704 and 1705. A copy of a summary is attached for your use. Please provide a list of special inspectors and their qualifications. Special inspector shall provide this office with a final report documenting required special inspections and correction of any discrepancies noted in the inspections as required by IBC Section 1704.2.4. A certificate of occupancy may not be issued for this project until the final report is received by this office.(9/21 Have the structural engineer remove the statement on sheet S002 and return the sheet) |
Inspections |
Open |
Provide information on compliance with the International Energy Conservation Code 2018. Comply with IECC Sections 401-405 or 407 as required. Computer-generated documentation (e.g. ComCheck) will be allowed to indicate total building performance as per IECC Section 407.6. Your summary must include building envelope, mechanical systems, water heating, interior lighting and electrical power systems.(9/21 Envelope only provided.) |
Inspections |
Resolved |
The registered designer for this project shall approve the engineered truss design drawings as they become available and forward them to this office for review.(9/21 Deferred) |
Inspections |
Resolved |
There have been no plans submitted for the systems for this project. These systems (Plumbing, Mechanical and Electrical) shall comply with all the requirements of the City of Fargo and its adopted codes. These plans will be allowed as deferred submittals per IBC Section 107.3.4.1. Please review and approve these plans for compliance and forward them to this office for our review. No work can start on these systems until approved. |
Inspections |
Resolved |
All exterior doors shall have landings per IBC Section 1010.1.5. |
Inspections |
Resolved |
Provide the updated structural plans for the mezzanine. |